DRF-FR
DRF-FR Freqency Input Signal Conditioner

DRF-FR : DRF-FR Freqency Input Signal Conditioner
Kliknìte zde pro vìtší obrázek.
  NPN, PNP, NAMUR, Voltage Pulse, Voltage AC (up to 200 Vac)
  Frequency Signals from 10 Hz up to 50 KHz
  Accuracy 0.2%
  Excitation Voltage 15 Vdc (20 mA) or 9V2 for NAMUR
  Galvanic Isolation between Input, Output and Power
  Part of a Comprehensive Family of Signal Conditioners

The DRF series DIN rail signal conditioners are designed to accept a broad range of input signals, such as ac and dc voltage and current, frequency, temperature (thermocouple and RTD), and process transducers, and provide standard process outputs of either 4 to 20 mA, or 0 to 10 Vdc. The DRF series feature a modern housing design, that is easily mounted on standard 35 mm DIN rails. Connections are safely and securely made through pluggable screw terminal connectors, with input and output connections on the opposite sides of the module.

The DRF-FR signal conditioner accepts a frequency input and provides an isolated 0 to 10 Vdc or 4 to 20 mA output. Models are available with three different power options, 24 Vdc, 120 Vac and 240 Vac.

The DRF-FR are ideally suited for industrial applications. All models mount on a standard 35mm DIN rail and provide galvanic isolation between input, output and power up to 3500 Veff . Module response time is 250 ms or less.

Adjustable Input Ranges
The front door of the housing provides easy access span and offset potentiometers which may be used field adjust the input and output signal range. The ranges shown in the Range Table below are supported.

Range CodeRange
20HZ0 to 20 Hz
40HZ0 to 40 Hz
60HZ0 to 60 Hz
100HZ0 to 100 Hz
200HZ0 to 200 Hz
300HZ0 to 300 Hz
500HZ0 to 500 Hz
1KHZ0 to 1 KHz
 
Range CodeRange
2KHZ0 to 2 KHz
3KHZ0 to 3 KHz
5KHZ0 to 5 KHz
10KHZ0 to 10 KHz
20KHZ0 to 20 KHz
30KHZ0 to 30 KHz
50KHZ0 to 50 KHz


Isolation
The input, output and power circuits are isolated by 3500 volts of galvanic isolation. The isolation protects against potentially damaging voltages from passing through the signal conditioners into connected systems. The isolation also provides improved measurement accuracy by minimizing the effects of ground loops and electrical noise.

Outputs
Each DRF series signal conditioner is available with current and voltage output (only one may be used at a time). Available output types include 4 to 20 mA or 0 to 10 Vdc. Although pre-configured before shipping from the factory, the output may be changed through an internal jumper change. Standard outputs are linear and proportional to the signal input.


SPECIFICATIONS

Signal Type: NPN, PNP, NAMUR, Voltage Pulse, AC up to 200 Vac (2 ranges < 24 Vac and < 200 Vac)
Accuracy: <0.2% full scale
Linearity: <0.1% full scale
Thermal Drift: 250 ppm/°C typical (max <200ppm/°C)

Response Time
0 to 100 Hz:
<300 mS (90% of signal)
0 to 500 Hz: <250 mS (90% of signal)
0 to 5 KHz: <200 mS (90% of signal)
0 to 50 KHz: <150 mS (90% of signal)

Impedance
Voltage Input:
(<24 Vac Range): 100 KΩ
Voltage Input: (<200 Vac Range): 1 M
PNP and NPN Input: 10 KΩ
NAMUR Input: 1 KΩ

Over Range Protection
Voltage Input (<24 Vac Range):
75 V
Voltage Input (<200V ac Range): 300 V
PNP and NPN Input: 35 V
NAMUR Input: Always powered by 9V2
 

Power: 24 Vdc ±10%, 230 Vac ±10% 50/60 Hz, 115 Vac ±10% 50/60 Hz
Power Consumption: <3.8 VA

Output: 4 to 20 mA and 0 to 10 Vdc
Maximum Voltage Output: 11 Vdc approx.
Minimum Voltage Output: -1 Vdc approx.
Minimum Load Resistance (Voltage): >1 KΩ Maximum Current Output: 22 mA approx.
Maximum Current Output: -1.5 mA approx.
Maximum Load Resistance (current): >400 Ω
Electrical Connections: Plug-in screw terminals
Protection: IP-30

MECHANICAL DIMENSIONS
Weight:
(DC Powered Models): 120 g (4.2 oz)
(AC Powered Models): 200 g (7 oz)
Dimensions:
(DC Powered models):
110 H x 22.5 W x 93 mm D (4.3 x 0.9 x 3.7")
(AC Powered models):
110 H x 37 W x 93 mm D (4.3 x 1.46 x 3.7")
Operating Temperature: 0 to 60°C (32 to 140°F)
Storage Temperature: -20 to 70°C (-4 to 158°F)


 Èíslo modelu  Cena (bez DPH)  Popis  Ks
 DRF-FR-115VAC-5KHZ-4/20    6,600.00 Kč   Frequency signal conditioner with 115Vac power, 0-5KHz input range and 4-20mA output
 DRF-FR-115VAC-1KHZ-0/10    6,600.00 Kč   Frequency signal conditioner with 115Vac power, 0-1000Hz input range and 0-10Vdc output
 DRF-FR-115VAC-100HZ-0/10    6,600.00 Kč   Frequency signal conditioner with 115Vac power, 0-100Hz input range and 0-10Vdc output
Obsah košíku Vyprázdnit košík Objednat
 * využijte možnost konzultovat ceny pøímo s našimi prodejci  (tel: 596 311 899 - prodejní oddìlení, e-mail: viz. kontaktní informace)
 Poznámka: All models come with a complete user's manual.
 Pøíklad objednávky: (1) DRF-FR-115VAC-5KHZ-4/20 DRF freqency input model, 115 Vac power, 0 to 5 KHz range and 4 to 20mA output = 6,600.00 Kč

(1) (2) (3)
DRF-FR- - -
Popis voleb
(1) Power
  Vyberte 24VDC pro 24 Vdc, 115VAC pro 115 Vac
(2) Input Range
  Vyberte 20HZ pro 0 to 20 Hz, 40HZ pro 0 to 40 Hz, 60HZ pro 0 to 60 Hz, 100HZ pro 0 to 100 Hz, 200HZ pro 0 to 200 Hz, 300HZ pro 0 to 300 Hz, 500HZ pro 0 to 500 Hz, 1KHZ pro 0 to 1000 Hz, 1KHZ pro 0 to 1 KHz, 2KHZ pro 0 to 2 KHz, 3KHZ pro 0 to 3 KHz, 5KHZ pro 0 to 5 KHz, 10KHZ pro 0 to 10 KHz, 20KHZ pro 0 to 20 KHz, 30KHZ pro 0 to 30 KHz, 50KHZ pro 0 to 50 KHz
(3) Output
  Vyberte 4/20 pro 4 to 20ma, 0/10 pro 0 to 10Vdc
 Poznámka: ne všechny kombinace jsou správné, ovìøte si správnost èísla modelu.

 Literatura
   Stáhnout kompletní specifikace produktu ve formátu PDF
 Manuály
   Stáhnout  DRF-FR Series - Frequency Input Signal Conditioners
 Souvísející odkazy
   DRF-TC: Thermocouple Input Signal Conditioner
   DRF-RTD: RTD Input Signal Conditioner
   DRF-RES and DRF-POT: Resistance and Potentiometer Input Signal Conditioners
   DRF-PR: DRF-PR Process Input Signal Conditioners
   DRF-LC: DRF-LC Load Cell Input Signal Conditioner
   DRF-IDC and DRF-IAC: DC and AC Current Input Signal Conditioners
   DRF-VDC and DRF-VAC: DC and AC Voltage Input Signal Conditioners