1 rok záruka CE RoHS
  • 100 Ω Platinum (Pt100) RTD Element, 0.00385 Curve
  • 2 or 3 Wire Configuration
  • 0.2% Accuracy
  • Cable Resistance Compensation up to 10 Ω
  • Upscale Break Protection
  • Response Time < 250 mS
  • Galvanic Isolation Between Input, Output and Power
Převodníky signálů - Zobrazit související produkty

Popis

Find how signal conditioning works on this link.

The DRF series DIN rail signal conditioners are designed to accept a broad range of input signals, such as ac and dc voltage and current, frequency, temperature (thermocouple and RTD), and process transducers, and provide standard process outputs of either 4 to 20 mA, or 0 to 10 Vdc. The DRF series feature a modern housing design, that is easily mounted on standard 35 mm DIN rails. Connections are safely and securely made through pluggable screw terminal connectors, with input and output connections on the opposite sides of the module.

The DRF-RTD signal conditioners accept 2 or 3 wire 100Ω platinum RTDs (Pt100) as input and provide an isolated 0 to 10 Vdc or 4 to 20 mA output. Models are available with three different power options,
24 Vdc, 115 Vac and 230 Vac.

The DRF-RTD are ideally suited for industrial applications. All models mount on a standard 35 mm DIN rail and provide galvanic isolation between input, output and power up to 3500 Veff (model specific). Module response time is 250 mS or less.

Range Code Table for DRF-RTD
Range CodeRange
-25/75C-25 to 75°C
0/100C0 to 100°C
0/200C0 to 200°C
0/300C0 to 300°C
0/450C0 to 450°C
0/600C0 to 600°C


SPECIFICATIONS

RTD: 2 or 3 wire 100Ω platinum
RTD: α=0.00385
Accuracy: <0.2% full scale
Linearity: <0.1% full scale
Thermal Drift: 250 ppm/°C typical
Response Time: <250 mS (90% of signal)
RTD Excitation: 1 Vdc
Input Impedance: Measured with a "Wheatstone" bridge. Bridge to positive through a 100 . resistance, Bridge to negative through a 10 KΩ resistance

Power: 24 Vdc ±10%, 230 Vac ±10% 50/60 Hz, 115 Vac ±10% 50/60 Hz
Power Consumption: <3.8 VA
Output: 4 to 20 mA and 0 to 10 Vdc
 

Maximum Voltage Output: 11 Vdc approx.
Minimum Voltage Output: -1 Vdc approx.
Minimum Load Resistance (Voltage): >1 KΩ Maximum Current Output: 22 mA approx.
Maximum Current Output: -1.5 mA approx.
Maximum Load Resistance (current): >400 Ω

Electrical Connections: Plug-in screw terminals
Protection: IP-30

MECHANICAL DIMENSIONS
Weight:
(DC Powered Models): 120 g (4.2 oz)
(AC Powered Models): 200 g (7 oz)
Dimensions:
(DC Powered models):
110 H x 22.5 W x 93 mm D (4.3 x 0.9 x 3.7")
(AC Powered models):
110 H x 37 W x 93 mm D (4.3 x 1.46 x 3.7")
Operating Temperature: 0 to 60°C (32 to 140°F)
Storage Temperature: -20 to 70°C (-4 to 158°F)
Tabulka pro objednání(Vyberte si model a zadejte počet kusů)
Číslo modelu/ Popis
Kusů
RoHS
Popis
Below are examples of popular models. See the Part Number Builder to order any available model.
DRF-RTD-230VAC-0/100C-4/20 Star
5,850Kč
Dostupnost: 8 týdny
V souladu s RoHS
RTD signal conditioner with 0 to 100C range, 4 to 20mA output and 230Vac power
DRF-RTD-24VDC-0/100C-4/20 Star
5,850Kč
Dostupnost: 8 týdny
V souladu s RoHS
RTD signal conditioner with 0 to 100C range, 4 to 20mA output and 24Vdc power
DRF-RTD-115VAC-0/100C-4/20 Star
5,850Kč
Dostupnost: 8 týdny
V souladu s RoHS
RTD signal conditioner with 0 to 100C range, 4 to 20mA output and 115Vac power
DRF-RTD-24VdC--50/150C-4/20 Star
5,850Kč
Dostupnost: 8 týdny
V souladu s RoHS
RTD signal conditioner with -50 to 150C range, 4 to 20mA output and 24Vdc power
DRF-RTD-115VAC-0/200C-4/20 Star
5,850Kč
Dostupnost: 8 týdny
V souladu s RoHS
RTD signal conditioner with 0 to 200C range, 4 to 20mA output and 115Vac power
DRF-RTD-230VAC--25/75C-0/10 Star
5,850Kč
Dostupnost: 8 týdny
V souladu s RoHS
RTD signal conditioner with -25 to 75C range, 0 to 10Vdc output and 230Vac power
Všechny ceny zobrazeny v Kč (bez DPH)
Příklad objednávání: (1) DRF-RTD-24VDC-0/100C-4/20 RTD signal conditioner with 0 to 100C range, 4 to 20mA output and 230Vac power, 5,850Kč

Tvorba čísla modelu

Sestavte si vlastní číslo modelu níže
Popis voleb:


(1) Power vybrat z:
115VAC pro 115 Vac power
230VAC pro 230 Vac power
24VDC pro 24 Vdc power

(2) Range Code vybrat z:
-25/75C pro -25 to 75 degree C
-50/150C pro -50 to 150 degree C
0/100C pro 0 to 100 degree C
0/200C pro 0 to 200 degree C
0/300C pro 0 to 300 degree C
0/450C pro 0 to 450 degree C
0/600C pro 0 to 600 degree C

(3) Output vybrat z:
4/20 pro 4 to 20 mA
0/10 pro 0 to 10Vdc
Poznámka: Všechny kombinace nemusí být správné, ověřte si správnost čísla modelu.