Thermocouple Input DIN Rail Signal Conditioners

4,350Kč DRSL-TC-ISO

1 rok záruka CE RoHS
  • DRSL-TC Non-Isolated and DRSL-TC-ISO Isolated Models
  • Accepts Type J and Type K Thermocouples
  • Pre-Calibrated Temperature Ranges Selectable via Dip-Switches
  • Slimline Housing—Only 6 mm (0.24") Wide
  • High Accuracy
  • Fast Response Time <30 ms/300 ms (Selectable)
  • Excellent EMC Performance and 50/60 Hz Noise Suppression
Procesní měřící a řídící zařízení - Zobrazit související produkty

Popis

The DRSL-TC Series thermocouple input DIN rail signal conditioners provide a competitive choice in terms of both price and technology for interfacing thermocouple inputs to SCADA systems or PLC equipment.

The DRSL-TC and DRSL-TC-ISO can be used for signal conversion of standard Type J or K thermocouple inputs into unipolar analog signals.

The DRSL-TC-ISO isolated model offers 3-way isolation between input, output and supply and provides surge suppression and protects control systems from transients and noise. Low power consumption facilitates DIN rail mounting without the need for any air gap. Easy configuration of more than 1000 factory calibrated measurement ranges is done via DIP-switches. The unit operates over a wide temperature range from -25 to 70°C (-13 to 158°F).

SPECIFICATIONS
INPUT
Type: J or K thermocouple
Temperature Range
    Type J: -100 to 1200°C (-148 to 2192°F)
    Type K: -180 to 1372°C (-292 to 2501°F)
Sensor and Cable Specifications: 5 kΩ per wire
Cold Junction Compensation (CJC): Internal or external (selectable)
CJC Accuracy via External CJC (Pt100 RTD Sensor): Better than ±0.15°C (DRSL-TC-ISO only)
CJC via Internally Mounted Sensor: Better than ±2.5°C
Open Thermocouple Detection: Yes (DIP switch selectable upscale or downscale)

OUTPUT
Current Output
Programmable Signal Ranges: 0 to 20 and 4 to 20 mA
Range Limits (NAMUR NE43 Out of Range): Below 3.8 mA or above 20.5 mA for 4 to 20 mA output; 0 mA or above 20.5 mA for 0 to 20 mA output
Sensor Error Detection (Dip Switch Selectable for Enable or None): Below 3.5 mA or above 23 mA for 4 to 20 mA output; 0 mA or above 23 mA for 0 to 20 mA output
Incorrect DIP-Switch Setting Identification: 0 mA
Output Error Level: DIP switch selectable for upscale or downscale
Load: 21 mA/600 Ω /12.6V max
Load Stability: ≤0.01% of span/100 Ω
Voltage Output
Programmable Signal Ranges: 0 to 10V, 2 to 10V, 0 to 5V and 1 to 5V
Range Limits (Out of Range): Range ±2.5%
Incorrect DIP Switch Setting Identification: 0V
Load: >10 kΩ min

GENERAL
Supply Voltage:
DRSL-TC: 16.8 to 31.2 Vdc via connectors
DRSL-TC-ISO: 16.8 to 31.2 Vdc via power rail or connectors
Power Consumption: 0.7 W max
Internal Consumption: 0.65 W max
Isolation (DRSL-TC-ISO Only): Input/output/supply
Isolation Voltage, Test (DRSL-TC-ISO Only): 2.5 kVac (reinforced)
Isolation Voltage, Working (DRSL-TC-ISO Only): 300 Vac
Status LED: Green LED indicates operational status of the unit and input sensor
    Normal Operation: Flashes for 15 ms at 13 Hz rate
    Sensor Error: Flashes for 15 ms at 1 Hz rate
    Incorrect DIP Switch Setting: Flashes for 500 ms at 1 Hz rate
    Hardware Failure: LED off
Signal/Noise Ratio: >60 dB
Response Time (0 to 90%, 100 to 10%): <30 ms/300 ms (selectable, provides either fast response or signal dampening as needed)
Accuracy:
    DRSL-TC: Better than 1.0°C or ±0.1% of selected input range
    DRSL-TC-ISO: Better than 0.5°C or ±0.05% of selected input range
Temperature Coefficient: ≤±0.1°C/°C or ≤±0.01%/°C
EMC Immunity Influence: <±0.5% of span
Extended EMC Immunity NAMUR NE 21, A Criterion, Burst: <±1% of span (span = selected input range)

ENVIRONMENTAL
Operating Temperature: -25 to 70°C (-13 to 158°F)
Storage Temperature: -40 to 85°C (-40 to 185°F)
Calibration Temperature: 20 to 28°C (68 to 82°F)
Relative Humidity: 0 to 95% RH non-condensing
Protection Degree: IP20
Installation Area: Pollution degree 2 and measurement/overvoltage category II

MECHANICAL
Dimensions: 113 H x 6.1 W x 115 mm D (4.4 x 0.24 x 4.5")
Weight: 70 g (0.15 lb) approx
DIN Rail Type: DIN EN 60715 - 35 mm
Wire Size: 0.13 x 2.5 mm²/ AWG 26 to 12 stranded wire
Screw Terminal Torque: 0.5 Nm
Tabulka pro objednání(Vyberte si model a zadejte počet kusů)

Co koupili ostatní: Když vidíte tuto ikonu, klikněte na ní a uvidíte seznam zboží, které nakoupili ostatní lidé, když si objednali tento model.

Číslo modelu/ Popis
Kusů
RoHS
Popis
  
DRSL-TC Star
3,300Kč
Dostupnost: 2 týdny
V souladu s RoHS
Non-isolated thermocouple input DIN rail signal conditioner
Klikněte pro rozbalení/sbalení seznamu zobrazujícího co nakoupili otatní s tímto produktemDRSL-TC-ISO
DRSL-TC-ISO Star
4,350Kč
Dostupnost: 5 týdny
V souladu s RoHS
Isolated thermocouple input DIN rail signal conditioner
Accessories
  
DRSL-PWR-RAIL Star
3,300Kč
Dostupnost: 4 týdny
V souladu s RoHS
Power rail (with cover and two end covers, one right hand and one left hand), 1 m (3.3') length for use with DRSL-TC-ISO only
Klikněte pro rozbalení/sbalení seznamu zobrazujícího co nakoupili otatní s tímto produktemDRSL-PCU
DRSL-PCU Star
2,400Kč
Dostupnost: 2 týdny
V souladu s RoHS
Power connector unit, 24 Vdc/2.5 A output to power rail for use with DRSL-TC-ISO only
  
DRSL-MOD-STOP Star
150Kč
Dostupnost: 2 týdny
V souladu s RoHS
Module stop (screwed onto power rail to support and hold mounted devices)
Všechny ceny zobrazeny v Kč (bez DPH)
Příklad objednávání: (1) DRSL-MOD-STOP Module stop (screwed onto power rail to support and hold mounted devices), 150Kč  plus (1) DRSL-PCU Power connector unit, 24 Vdc/2.5 A output to power rail, 2,400Kč  plus (1) DRSL-PWR-RAIL Power rail (with cover and two end covers, one right hand and one left hand), 1 m (3.3') length, 3,300Kč  plus (1) DRSL-TC-ISO Isolated thermocouple input DIN rail signal conditioner, 4,350Kč, 150 + 2,400 + 3,300 + 4,350 = 10,200Kč